Permit: T10CM01097

Parcel: 11108175F


Addresses:

3749 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/20/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/16/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/25/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT UNDERSTAND PANEL DIRECTORY-TO BE PER 408.4
2) GROUND TIME CLOCK
3) SECURE DEVICE TO WALL, PROPERLY TERMINATE GROUND CONDUCTOR AND NEED ARC SHIELD
4) WILL CHECK BATH FIXTURE FOR 410.43 (6) NEXT TIME
ROOF:
1) INSTALL ROOF STAND FOR A/C DISCONNECT
2) TIGHTEN LOOSE FITTINGS
3) GROUNDING EQUIPMENT CONDUCTOR TO SMALL 250.122
4) BUSHING NEEDED FOR CONDUCTOR #4 AND LARGER 300.4