Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM01089
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/29/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
10/26/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CUT UP ORANGE EXTENSION CORD NOT ALLOWED-USE APPROVED CORD AND PLUG 2) PROPERLY SUPPORT RECEPTS TO INDUSTRIAL COVER 3) ALL KITCHEN RECEPTS TO BE GFCI PROTECTED 210.8 4) FIXTURES TO HAVE DISCONNECTING MEANS 410.73 (6) 5) M/C CABLE TO TERMINATE-NOT SHOVED DOWN PIPE 6) CONTRACTORS TO BE LISTED 7) EM LIGHTS TO BE ON CIRCUIT FOR AREA SECURED 700.12 (F) 8) FILL UNUSED OPENING IN GUTTER 9) PLEASE PROVIDE ROOF ACCESS 10) CLEAN EXCESS DIRT AND FOREIGN MATERIAL OUT OF BOTTOM OF SUB PANEL |
|
10/20/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) GENERAL CONTRACTOR WILL RECALL INSPECTION FOR MONDAY |
|
10/19/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection |