Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01087
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/29/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/27/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT WIRES NEEDED FOR EXIT SIGN BOXES 2) VDV CABLING TO BE AS PER 725.3 + 24, 800.3 + 24 AND 300.11 3) SUPPORT M/C CABLE WITHIN 12" OF BOXES AND UPON EXIT OF DRYWALL 4) PLANS NOT REFLECTIVE OF WORK INSTALLED, PLEASE REVISE AND HAVE APPROVED BY CITY BEFORE FINAL |