Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10CM01087

Parcel: 12411021E


Addresses:

1800 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM01087

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/29/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/27/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT WIRES NEEDED FOR EXIT SIGN BOXES
2) VDV CABLING TO BE AS PER 725.3 + 24, 800.3 + 24 AND 300.11
3) SUPPORT M/C CABLE WITHIN 12" OF BOXES AND UPON EXIT OF DRYWALL
4) PLANS NOT REFLECTIVE OF WORK INSTALLED, PLEASE REVISE AND HAVE APPROVED BY CITY BEFORE FINAL