Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01085
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ROOF DISCONNECT PUT BOND BUSHINGS 2) PV INTERVERTER DISCONNECT EMT PIPE NOT IN CONNECTOR ALL THE WAY 3) PV METER BASE LUG, SCRAPE OFF PAINT |
|
07/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND BUSHING ON CONCENTRIC KNOCKOUTS 2) GROUNDING ELECTRODE TO BE STRAPPED TO WALL 3) PRINT CALLS FOR EMT NOT SEAL TIGHT 4) PANELS PIPE RUN LOOSE |