Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/25/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*. 1) EMT HAS TO BE STRAPPED ADN USE DEEP STRUT 2) J-BOX HAS TO BE BONDED 3) COUPLING PANEL RACK TO BE GROUNDED 4) 1/2 EMT CONNECTORS ON BELL BOX ARE LOOSE ON ROOF 5) PANEL HAST TO HAVE PLASTIC BUSHING FOR HOME RUNS |