Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/07/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EM LIGHT AT FRONT OF STORE TO BE TIED INTO LIGHTING CIRCUIT FOR AREA 2) EQUIPMENT GROUND FOR WATER HEATER TO BE #10 30 AMP CIRCUIT NEC 250.122 3) INSTALL ALL MOUNTING HARDWARE FOR RECEPTS IN REVISED INDUSTRIAL COVERS 4) RECEPT UNDER PANEL TO BE PROPERLY MOUNTED OR REMOVED. IF STAYING, NEEDS TO BE GFI PROTECTED |