Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01056
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/07/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EM LIGHT AT FRONT OF STORE TO BE TIED INTO LIGHTING CIRCUIT FOR AREA 2) EQUIPMENT GROUND FOR WATER HEATER TO BE #10 30 AMP CIRCUIT NEC 250.122 3) INSTALL ALL MOUNTING HARDWARE FOR RECEPTS IN REVISED INDUSTRIAL COVERS 4) RECEPT UNDER PANEL TO BE PROPERLY MOUNTED OR REMOVED. IF STAYING, NEEDS TO BE GFI PROTECTED |