Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/21/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ELECTRICAL LOAD CALC TO DETERMINE IF THE EXISTING 100 AMP SERVICE PANEL NEEDS TO BE UPGRADED 2) PROVIDE SEDIMENT TRAP AT GAS PIPING TO RTU 3) REMOVE BLACK GROUND WIRE AND REPLACE WITH GREEN 4) ALL DUCT ON ROOF TO HAVE A MINIMUM R-VALUE OF 8, 1" DUCT LINER ONLY CARRIES A VALUE OF R-4.2, 2" DUCT LINE IS REQUIRED |