Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/02/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/26/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AC & DC DISCONNECTS TO BE GROUPED PER NEC 690.14 (C) (5). TALKED WITH RAY MAJUTA HE IS IN AGREEMENT
05/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECTS FOR SYSTEM TO BE GROUPED
2) INSTALL WORKING LABELS PER PLANS AND NEC 690
3) PANELS APPEAR TO BE UNLISTED
4) EQUIPMENT TO BE OFF AND OPEN FOR INSPECTION
5) INSTALL PROPER FLASHING AT ROOF PENETRATIONS
6) MISSING #8 GEC
7) MISSING DC COMBINER BOX
8) NEXT INSPECTION EQUIPMENT TO BE OFF AND OPEN OR WILL HAVE TO PAY REINSPECTION FEE
05/13/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*