Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE MIN 1/8 PER FT SLOPE ON ALL SECTIONS OF CONDENSATE DRAIN TERMINATE 3/8 COPPER DRAIN INTO PVC W/ A FITTING. PROVIDE SUPPORT FOR 3/8 DRAIN LINE PROVIDE THE REQUIRED GFI SERVICE RECPECTACLE ON ROOF |