Permit: T10CM01040

Parcel: 135103040


Addresses:

7422 E 32ND ST

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/12/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE MIN 1/8 PER FT SLOPE ON ALL SECTIONS OF CONDENSATE DRAIN TERMINATE 3/8 COPPER DRAIN INTO PVC W/ A FITTING. PROVIDE SUPPORT FOR 3/8 DRAIN LINE
PROVIDE THE REQUIRED GFI SERVICE RECPECTACLE ON ROOF