Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/09/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO SEE ALL JOINTS OF DRYER VENT. VENT CANNOT BE FASTENED WITH SCREWS. SHORT POP RIVETS WOULD BE OK. DO NOT USE A FLUE CAP ON A DRYER VENT. TERMINATE PER DETAIL ON PLANS 2) PROVIDE A PROTECTIVE COTAING ON EXPOSED ARMAFLEX. SUPPORT REFER LINES AND CONDUIT TO CONDENSOR ON ROOF. DISCONNECT ON CONDENSOR IS BLOCKING DATA PLATE INFO 3) TERMINATE CONDENSATE TO AN APPROVED LOCATION. PAINT EXPOSED PVC WITH LATEX PAINT. SUPPORT EVERY 4' 4) PROVIDE A FRESH AIR INTAKE AND BALANCE AS PER PLANS |