Permit: T10CM01035

Parcel: 114469370

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/10/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/09/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) NEED TO SEE ALL JOINTS OF DRYER VENT. VENT CANNOT BE FASTENED WITH SCREWS. SHORT POP RIVETS WOULD BE OK. DO NOT USE A FLUE CAP ON A DRYER VENT. TERMINATE PER DETAIL ON PLANS
2) PROVIDE A PROTECTIVE COTAING ON EXPOSED ARMAFLEX. SUPPORT REFER LINES AND CONDUIT TO CONDENSOR ON ROOF. DISCONNECT ON CONDENSOR IS BLOCKING DATA PLATE INFO
3) TERMINATE CONDENSATE TO AN APPROVED LOCATION. PAINT EXPOSED PVC WITH LATEX PAINT. SUPPORT EVERY 4'
4) PROVIDE A FRESH AIR INTAKE AND BALANCE AS PER PLANS