Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2010 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 08/20/2010 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 08/12/2010 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECT SLOPE 905.2 REQUIRES THAT THE VENT INVORT BO TAKEN OFF ABOVE THE CENTER LINE 905.5 POINT OF VENT MAY NOT BE BELOW WEIR. PROVIDE DRAINAGE FHANGS AS REQUIRED. (SWOOPS) FLOOR DRAIN AT WASHER IS NOT SHOWN ON PLAN. AND REQUIRES A PLAN REVISION. WET VENT NO SIZED PER CODE 908-2 P-6 NOT SIZED PER PLAN ALSO PROVIDE MIN TRAP ARM DISTANCE FD NOT PER PLAN SPOT POX ROUTING NOT AS SHOWN ON SCHOMATIC PROVIDE A LO HOR FROM YOUR ? FOR ALL CHANGES TO PLAN. REDLINE CHANGES ON PLAN. PROVIDE CLEAN FILL AND PROTECTION OF PIPING |
|
| 08/10/2010 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/09/2010 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* |