Inspection History: ELECTRIC - FINAL

Permit Number - T10CM01029

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/12/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/11/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) EITHER USE HANDLE TIES FOR ALL CIRCUITS OR REMOVE UNUSED CIRCUIT CONDUCTOR FOR MOD FURNITURE 604.5
08/10/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL HANDLE TIES PER LAST INSPECTION
08/06/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXISTING FEEDER TO NEW PANEL HAS NO EQUIPMENT GROUND HAVE GROUNDING TYPE RECEPTS IN MODULAR FURNITURE
2) CALLED ENGINEER TO DISCUSS ISSUES AND HE WILL ADDRESS THIS PROBLEM
3) BRANCH CIRCUITS FEEDING MODULAR FURNITURE TO BE CONNECTED WITH APPROVED HANDLE TIES ON BREAKER
08/02/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE REVISION AND INSPECTION FOR MODULAR FURNITURE, NOT SHOWN ON THIS PLAN
07/30/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE DISCONNECT SWITCH FOR FC UNIT IN SERVER ROOM-SEE PLANS
2) ISOLATE NEUTRAL FROM GROUNDS-NEUTRALS NOT TO BE BONDED IN PANEL 'A'. THIS IS A UNDERGROUND SYSTEM, CANNOT USE GROUNDED RECEPTS ON A UNGROUNDED SYSTEM UNLESS GFI AHEAD OF CIRCUIT PER 250 NEC