Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01029
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/11/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) EITHER USE HANDLE TIES FOR ALL CIRCUITS OR REMOVE UNUSED CIRCUIT CONDUCTOR FOR MOD FURNITURE 604.5 |
|
08/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL HANDLE TIES PER LAST INSPECTION |
|
08/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXISTING FEEDER TO NEW PANEL HAS NO EQUIPMENT GROUND HAVE GROUNDING TYPE RECEPTS IN MODULAR FURNITURE 2) CALLED ENGINEER TO DISCUSS ISSUES AND HE WILL ADDRESS THIS PROBLEM 3) BRANCH CIRCUITS FEEDING MODULAR FURNITURE TO BE CONNECTED WITH APPROVED HANDLE TIES ON BREAKER |
|
08/02/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE REVISION AND INSPECTION FOR MODULAR FURNITURE, NOT SHOWN ON THIS PLAN |
|
07/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE DISCONNECT SWITCH FOR FC UNIT IN SERVER ROOM-SEE PLANS 2) ISOLATE NEUTRAL FROM GROUNDS-NEUTRALS NOT TO BE BONDED IN PANEL 'A'. THIS IS A UNDERGROUND SYSTEM, CANNOT USE GROUNDED RECEPTS ON A UNGROUNDED SYSTEM UNLESS GFI AHEAD OF CIRCUIT PER 250 NEC |