Inspection History Details
Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/14/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/06/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO CHECK FOUND FOR $75.00 |
|
| 06/29/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/25/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KEYS IN LOCK BOX DO NOT OPEN DOORS |
|
| 06/23/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/18/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRICAL J-BOXES SHALL BE ACCESSIBLE 2) 1" CLEARANCE FROM COMBUSTIBLE REQUIRED AT WATER HEATER B-VENT 3) ALL METAL BOXES SHALL BE GROUNDED 4) COMBUSTION PROVIDED RELIEF REQUIRED FOR WATER HEATER 5) HOW IS HOUSE BEING HEATED ? MUST PROVIDE SOURCE 6) H2.5 TIES REQUIRED FROM RAFTERS TO DBL PLATES 7) $75.00 REQUIRED OWED AT THIS TIME FEES NOT AVAILABLE 8) PROTECT PTR LINE WITH BANG PLATES |