Permit: T10CM01024

Parcel: 10714376H


Addresses:

515 E GRANT RD #101


Inspection Status: Cancelled

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM01024

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Cancelled

Date Description Inspector Results Comments
08/02/2010 MECHANICAL - ABOVE CEILING Cancelled IVRS - RI canceled
07/30/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/28/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FLEX NOT TO EXCEED 3'
2) PROVIDE OBD'S PER PLANS
07/26/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE SHEET METAL HANGER STRAPS FOR FLEX DUCT AND PROVIDE METAL WORN DRIVE CLAMPS AT ALL CONNECTIONS. SEAL WITH DUCT TAPE
2) PROVIDE CONDENSATE DRAIN LINES
3) PROVIDE SUPPLY AIR TO RESTROOMS PER PLANS
4) SEE ENGINEER ABOUT TIME CLOCKS FOR RESTTROOM EXHAUST