Inspection History Details
Inspection Status: Cancelled
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2010 | MECHANICAL - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 07/30/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/28/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FLEX NOT TO EXCEED 3' 2) PROVIDE OBD'S PER PLANS |
|
| 07/26/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE SHEET METAL HANGER STRAPS FOR FLEX DUCT AND PROVIDE METAL WORN DRIVE CLAMPS AT ALL CONNECTIONS. SEAL WITH DUCT TAPE 2) PROVIDE CONDENSATE DRAIN LINES 3) PROVIDE SUPPLY AIR TO RESTROOMS PER PLANS 4) SEE ENGINEER ABOUT TIME CLOCKS FOR RESTTROOM EXHAUST |