Permit: T10CM01009

Parcel: 11105016B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01009

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/18/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
1. PROVIDE MINIMUM 3/4" CONDENSATE DRAIN FULL DISTANCE TO LAVATORY TAILPIECE.
2. PLUG UNUSED DRAIN IN CONDENSATE PAN
3. PROVIDE P-TRAP IN CONDENSATE PIPING
4. PROVIDE MEANS OF SECONDARY DRAIN OR SENSOR
5. ALL PVC JOINTS AND FITTINGS ARE TO HAV PRIMER APPLIED PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC
6. REFRIGERATION PIPING INSULATION IS TO CONTINUE COMPLETELY OVER CONDENSATE PAN SO AS NOT TO DRIP OUTSIDE OF PAN