Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM01009
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/18/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : 1. PROVIDE MINIMUM 3/4" CONDENSATE DRAIN FULL DISTANCE TO LAVATORY TAILPIECE. 2. PLUG UNUSED DRAIN IN CONDENSATE PAN 3. PROVIDE P-TRAP IN CONDENSATE PIPING 4. PROVIDE MEANS OF SECONDARY DRAIN OR SENSOR 5. ALL PVC JOINTS AND FITTINGS ARE TO HAV PRIMER APPLIED PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC 6. REFRIGERATION PIPING INSULATION IS TO CONTINUE COMPLETELY OVER CONDENSATE PAN SO AS NOT TO DRIP OUTSIDE OF PAN |