Permit: T10CM01000

Parcel: 137290370

Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
11/25/2015 BUILDING - PROGRESS Approved
07/21/2015 BUILDING - PROGRESS Partial Approval 1. ADD STRUTS TO POSTS AS DRAWN.
5. EXPOSE RAFTER CONNECTIONS TO TOP PLATE ON EXTERIOR WALL- 2 PLACES PER ROOM.
6. DO #6
04/16/2010 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REAR PORCH HEADERS 4 X 6 SPAN 12'
2) REAR PORCH RAFTERS 2 X 6 SPAN 13'
3) ADDITIONS 2 X 6 24" ON CENTER SPAN 13', SUBMIT ROOF PLAN WITH CROSS SECTION TO PLAN REVIEW FOR SPAN CALCULATIONS
4) EXPOSE ALL BEARING FOOTERS
5) EXPOSE RAFTER CONNECTIONS ADDITIONS BOTH ENDS 1 SPOT EACH ROOM TO VERIFY CONNECTION APPLICATION
6) EXPOSE ALL ELECTRICAL WORK FOR INSPECTION OR PROVIDE LETTER HEAD FROM LICENSED ELECTRICAL CONTRACTOR STATING ALL WORK TO CODE