Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM00989
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) AIR BALANCE OK 2) DUCT SMOKE DETECTOR TEST OK 3) OK FOR FINAL |
|
07/26/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE DRAIN NOT SOLDERED AT CONNECTION TO UNIT 2) ID DATA PLATE WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY 3) PROVIDE THE REQUIRED ECONOMIZER AS PER PLANS 4) RE-BALANCE OUTSIDE AIR 5) DUCT SMOKE DETECTOR TEST IS OK |