Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CONNTO TERMINATE IN WASTE VENT 2) NO ROOFTOP ACCESS ON SITE 3) ALL ITMES LISTED ON 04-15-10 ARE TO BE COMPLETE OR A RE-FEE WILL BE ADDED TO THIS PERMIT |
|
| 04/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE FACE PLATE ON ELECTRICAL PANEL 2) BREAKERS ARE TO BE LABELED 3) DO NOT USE WHITE WIRES FOR HOT LEGS 4) CONDENSATE PIPING TO BE BLOCKED UP OFF ROOF MIN. 1.5" 5) CONDENSATE TO TERMINATE WITHIN 6" OF GRADE, CONDENSATE TO BE COATED TO PROTECT FROM ENVIORMENT ELEMENTS 6) LOW VOLTAGE TO BE IN CONDUIT 7) UNIT IS UNDERFUSED, PROVIDE CORRECT FUSES 8) DUCT ON EXTERIOR TO BE MINIMUM R-8 |
|
| 04/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMITS AND PLANS (IF ANY) ARE TO BE ON SITE FOR INSPECTION |