Permit: T10CM00969

Parcel: 141340460

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T10CM00969

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
06/21/2010 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/14/2010 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
2ND FLOOR PLUMBING WET VENT IS NOT 6" ABOVE FLOOR LINE OF FIXTURES, BATHROOM ABOVE GARAGE
HANGER AT ROOF GIRDER NOT THE ONE PRESCRIBED BY THE ENGINEER
05/25/2010 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK TO COVER
2) NEED TRUSS REPAIR T.A. TRUSS AT DIAGONAL WALL 2ND FLOOR
05/21/2010 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED LADDER ACCESS
2) T.A. ROOF TRUSS AT 45 DEGREE WALL, HAS LARGE CRACK IN BOTTOM CHORD
3) HANGER 3 1/8 X 13.5 GW LAM ROOF TO BE A GLT3 WON'T WORK NEED ALTERNATE
4) CS14 COIL STRAPS 1ST-2ND FRONT #5 SHEAR