Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T10CM00938
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) FLANGES OK 2) YOU WILL NEED RWG TO APPROVES CHANGE FROM MOP BASIN TO JANITOR SINK-YOU MAY NEED TO PROVIDE A 2" P-TRAP |
|
05/11/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ONE FLANGE OK, OTHER FLANGE STILL NEEDS CORRECTING |
|
05/10/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PIPE IS TO EXTEND TO TOP OF FLANGE 2) FLANGE IS TO EXTEND 1/4" ABOVE FINISHED FLOOR |
|