Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/30/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK WALLS |
|
| 04/28/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GRID FIXTURES NEED SISMEC WIRES AND SECURE TO GRID, LIGHT SWITCHES TO BE GROUNDING TYPE 2) PROCEDURE ROOMS #1 AND 3 TO COMPLY WITH 517.13 NEC-THIS INCLUDES HOMERUNS. SEE NOTE #5 SHEET E1 PLANS |