Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2010 | ELECTRIC - FINAL | Approved | ||
| 05/20/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 2,3 & 4 NOT COMPLETED |
|
| 05/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO WORK PROGRESS |
|
| 04/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAINTAIN WORKING CLEARANCES 110.26 2) REDUCING WASHER IMPORPERLY INSTALLED 3) OPEN METER SOCKET TO INSPECT WIRING AND BONDING 4) BONDING NEEDED PER 250.64 5) PROPERLY INSTALL CUP WASHERS FOR GROUNDING |