Permit: T10CM00904

Parcel: 138071260


Addresses:

917 W CALLE ALVORD

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/03/2010 BUILDING - FINAL Approved IVRS - Inspection :*
04/29/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) $75.00 CHECK REQUIRED TO CITY OF TUCSON PRIOR TO FOLLOW UP EVALUATION
2) NOTES 2,3,4 & 9 FROM PREVIOUS
3) ADDITION IS NOT INSULATED
4) LETTER FROM LICENSED CONTRACTOR NOT SUFFICIENT, MENTIONS NOTHING ABOUT ELECTRICAL WORK DONE WITHOUT INSPECTION TO CODE FOR SAFETY: OUTLETS, WIRING AND FIXTURES IN UNPERMITTED ROOM
04/20/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE COMBUSTION RELIEF WATER HEATER ROOM LAUNDRY
2) OUTLETS TEST OPEN GROUND 2 WIRE CIRCUIT WITH GROUNDED OUTLETS
3) CLOSET LIGHT FIXTURE WITHIN 12" STACKABLE COMBUSTIBLES
4) EXPOSE ALL ELECTRICAL OR PROVIDE LETTER HEAD FROM LICENSED ELECTRIC CONTRACTOR STATING ALL ELECTRICAL IN ADDITION INSTALLED TO CODE FOR SAFETY
5) WINDOW MINIMUM OPENING MUST BE 20" TO MEET MINIMUM OPENING WIDTH FOR EGRESS
6) EXPOSE FOOTERS TO VERIFY DEPTH IN 2 LOCATIONS
7) PROVIDE ACCESS TO ATTIC IN CLOSET (LADDER)
8) CHECK REAR PORCH HARDWARE. BEAM TO POST AND RAFTER TO HEADER
9) INSTALL SMOKE ALARM WEST SIDE BEDROOM DOOR