Permit: T10CM00891

Parcel: 136382190


Addresses:

4688 S GOLDENROD PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/07/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
05/21/2010 PLUMBING - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Nobody on site
Pay reinspection fee prior to next inspection
05/19/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOBODY ON SITE, NO ACCESS
05/14/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS
2) DOORS LOCKED
04/28/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AN OVERFLOW SENSOR, USE PURPLE PRIMER ON PVC FITTINGS PRIOR TO GLUE
2) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTION
3) NO THREADS ALLOWED AT T & P TERMINATION
4) REMOVE DUCT TAPE FROM LINE SET ON ROOF. PROVIDE A PROTECTIVE COATING ON ARMAFLEX EXPOSED ON ROOF
5) TIGHTEN LOOSE ELECTRIC FITTING AT DISCONNECT
6) SHOW WHERE CONDENSATE TERMINATES