Permit: T10CM00886

Parcel: 115160510

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/23/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/22/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LIGHT FIXTURES (NEW OR RELOCATED) NEED SISMEC WIRES AND SECURED TO GRID
2) MC CABLE TO BE SUPPORTED PER CODE 12" + 6', SUPPORT WIRES TO BE TIED OFF BOTH ENDS 300.11 NEC
3) WHY DO NEW HOME RUNS CKT 13 & 14 ON 30 AMP CKT BREAKERS ??
04/08/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS, M/C CABLE ABOVE CEILING TO BE SUPPORTED PER CODE 12"-6' WHEN USING SISMEC WIRES USE APPROVED CLIPS, WIRES TO BE TIED OFF BOTH ENDS PER 300.11 NEC