Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM00886
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/22/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LIGHT FIXTURES (NEW OR RELOCATED) NEED SISMEC WIRES AND SECURED TO GRID 2) MC CABLE TO BE SUPPORTED PER CODE 12" + 6', SUPPORT WIRES TO BE TIED OFF BOTH ENDS 300.11 NEC 3) WHY DO NEW HOME RUNS CKT 13 & 14 ON 30 AMP CKT BREAKERS ?? |
|
04/08/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS, M/C CABLE ABOVE CEILING TO BE SUPPORTED PER CODE 12"-6' WHEN USING SISMEC WIRES USE APPROVED CLIPS, WIRES TO BE TIED OFF BOTH ENDS PER 300.11 NEC |