Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM00846
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2010 | ELECTRIC - FINAL | Approved | ||
07/30/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #3 PREVIOUS INSPECTION PER PLANS |
|
07/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE WRITE UP SPACE 160 2) CASH WRAP RECEPTS CALL FOR ? 3) FILL UNUSED OPENINGS IN BOXES AT CASH WRAP 4) PROTECT VDV CABELING FOR PHYSICAL PROTECTION 5) CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 6) EM LIGHTS TO BE ON CIRCUIT FOR AREA SERVED 700.12 (F) 7) VERIFY LISTING FOR LIGHTING CONTROL CABINET 8) FINISH PULLING VDV CABLING (#2) AND FIXTURE DISCONNECTS |
|
07/21/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECONNECT GROUNDING ELECTRODE CONDUCTOR 2. FINISH ELECTRIC AS PER PLANS OR REVISE PLANS 3. SERVICE FEEDERS NOT CONNECTED A REFEE MAY BE ASSESSED FOR UNNECESSARY INSPECTION |