Date Description Inspector Results Comments
08/02/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/16/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) MEETING TO DISCUSS INSTALLING CONDUCTORS TO SERVICE DISCONNECT IN GEAR
2) INSPECTOR ONLY NEEDS TO SEE TERMINATION OF CABLES TO RELEASE POWER FOR SPACE
06/23/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VERIFY LISTING FOR LIGHTING ?
2) OK WALL AND LID AT PANELS
06/07/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE BACK BRACING TO BOXES 312.23
2) OK WALLS AFTER CORRECTIONS
06/03/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT M/C CABLES AT SHALLOW STUDS
2) BROKEN M/C ARMOR
3) PROTECT VDV CABLING FROM SHARP METAL EDGES
4) PROTECT PVC CONDUITS AT BASE PLATE
5) OK PVC CONDUIT UNDER SLAB