Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/09/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) SMOKE CONTAINMENT TEST OK 2) TYPE 1 EXH/MVA INTERLOCK OK 3) HEAT SENSOR INTERLOCK OK 4) DUCT SMOKE DETECTOR TEST FAILED UNIT DID NOT SHUT DOWN 5) ALL ROOF TOP MECH. EQUIP. AND INSTALLATION OK |
|
| 09/08/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/24/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) W/H FLUE PIPE OK |
|
| 07/28/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |