Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH #3 & 7 |
|
| 09/08/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/02/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 2) EM LIGHT NOT WORKING DINING 3) TAPE MARKING TO ENCIRCLE CONDUCTOR-INSIDE MAKE FOR HOOD 4) DISHWASHER RECEPT TO BE GFCI 5) TIGHTEN LOOSE FITTING ON ROOF 6) TIME CLOCK NOT A DISCONNECTING MEANS AND FILL UNUSED OPENING 7) SEAL WALK IN BOX PER 300.7 8) SUPPORT VDV CABLING 725.24 |