Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10CM00839

Parcel: 11901076A


Addresses:

3386 S 6TH AV #120


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM00839

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/08/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/18/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT WIRES NEEDED FOR EXIT LIGHTS AND EM LIGHTS
2) PROPERLY SUPPORT VDV CABLING 725.3 + 24, 815.24, 820.24 AND 300.11
3) VERIFY BOX FILL ABOVE PANEL
4) WAITING ON OCCUPANCY CENSORS
07/28/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT M/C CABLES WITHIN 12"
2) PROPERLY STRAP EMT CONDUITS
3) PROTECT M/C CABLES AT SHALLOW STUDS
4) WILL NEED REVISIONS RESTAMPED BY FINAL