Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/20/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HAVE ELECTRICIAN CALL INSPECTOR-909-4749 TO RESCHEDULE INSPECTIONS |
|
| 04/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SERVICE NIPPLE OVER FILLED 2) PROTECT CONDUCTOR 300.4 3) GROUNDING CONDUCTOR TO BE SIZED PER 250.122 4) ONLY ONE CONDUCTOR PER TERMINAL LUG 5) LABEL CIRCUIT BREAKERS AND VERIFY ONLY 3 CIRCUIT TO ENTIRE HOUSE 6) MEHL ELECTRIC DOING WORK |