Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/09/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL ACCESS DOOR PER INSTALLATION INSTRUCTIONS 2) PROVIDE AIR BALANCE REPORT ON EXHAUST/MVA 3) PROVIDE SMOKE CONTAINMENT TEST ON HOOD, SEE PAGE 2 FOR CONT. 4) PROVIDE GREASE THRU ON ROOF TOP EXHAUST FAN 5) PROVIDE GASKET ON GREASE DUCT TO FAN CONNECTION 6) PROVIDE SUN SHIELD ON M.V.A. FLEX 7) ELECTRIC CONDUIT HANGING UP WHEN FAN IS OPENED 8) PROVIDE HEAT SENSOR INTER LOCK TEST 9) PROVIDE CLEAN EDGES ON SHEET METAL SURFACES UNDER AND AROUND HOOD. NO SHARP EDGES. USE ONLY SILICONE CAULKING IN HOOD AREA |
|
| 10/19/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/18/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/15/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/14/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/13/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/08/2010 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |