Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10CM00792

Parcel: 124050600


Addresses:

944 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM00792

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
11/09/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL ACCESS DOOR PER INSTALLATION INSTRUCTIONS
2) PROVIDE AIR BALANCE REPORT ON EXHAUST/MVA
3) PROVIDE SMOKE CONTAINMENT TEST ON HOOD, SEE PAGE 2 FOR CONT.
4) PROVIDE GREASE THRU ON ROOF TOP EXHAUST FAN
5) PROVIDE GASKET ON GREASE DUCT TO FAN CONNECTION
6) PROVIDE SUN SHIELD ON M.V.A. FLEX
7) ELECTRIC CONDUIT HANGING UP WHEN FAN IS OPENED
8) PROVIDE HEAT SENSOR INTER LOCK TEST
9) PROVIDE CLEAN EDGES ON SHEET METAL SURFACES UNDER AND AROUND HOOD. NO SHARP EDGES. USE ONLY SILICONE CAULKING IN HOOD AREA
10/19/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/18/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/15/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/14/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/13/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/08/2010 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*