Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM00792
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2010 | ELECTRIC - ABOVE CEILING | Approved | ||
11/05/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PANEL SCHEDULE TO BE UPDATED AND ACCURATE, ALSO MUST HAVE 36" CLEAR SPACE IN FRONT 110.26 NEC 2) ALL 110V KITCHEN RECEPTS MUST BE GFI PROTECTED 210.8 NEC 3) CEILING FANS TO BE MTD. ON APPROVED FAN BOXES |