Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM00789
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED LETTER FOR FUSES 2) OK ELECTRIC |
|
05/13/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
04/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLIMATIC HAS INSTALLED NUMEROUS CONTROL WORK- RACEWAYS AND RELAYS IN CABINETS ALL NEW WORK 2) COMPARTMENT NOT MANUFACTURE EQUIPMENT-NEED 3RD PARTY VERIFICATION OR WIRE AS REQUIRED 3) APPROVED SET NOT ON SITE 4) RECEIVED LETTER FOR CONDUIT AND CONDUCTORS |
|
04/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLANS CALL FOR 175 AMP FUSES 2) RACEWAY TO BE CONTINOUS TO DISCONNECT COMPARTMENT FOR SEGRIGATION OF CONDUCTOR THROUGHOUT 3) CONDUCTORS OUTDOORS TO BE XHHW PER PLANS 5) CONDUIT RUNS NOT TO BE OVER 360 DEGREE 6) PLANS CALL FOR 3/4" MINIMUM RACEWAY SIZE 7) WHERE IS PLANS FOR ? WORK ? |