Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: STUCCO MESH
Permit Number - T10CM00780
Inspection Description - STUCCO MESH
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2010 | STUCCO MESH | Approved | IVRS - Inspection :* | |
| 06/24/2010 | STUCCO MESH | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRE MESH SHALL BE NAILED 6" ON CENTER TOP & BOTTOM, CAULK ALL OPENINGS 2) STAPLE ALL WIRES WITHIN 12" OF J-BOXES 3) ISOLATE GROUNDS AND NEUTRALS FROM SUB PANEL |
|
| 06/17/2010 | STUCCO MESH | Denied | IVRS - Inspection : See detailed listing on site.| 999* |