Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T10CM00778
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2010 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
07/23/2010 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* 1) FINISH ALL PREVIOUS ITEMS BEFORE RECALL |
|
07/22/2010 | ELECTRIC - UFER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND METAL RACEWAY FOR GEC 250.64 (?) 2) CLOSE UNUSED CONDUIT OPENING ABOVE PANEL 3) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS AND FILL UNUSED OPENINGS 4) BOND CONTACTOR ENCLOSURE 5) FINISH INSTA HOTS AND LIGHTING AT SHELVES 6) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 7) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM FLOOR BOXES 8) PLEASE VERIFY LISTING FOR LIGHT ASSEMBLIES 9) SUPPORT M/C UP OFF FLOOR AT CASH BOX 10) PANEL DIRECTORY PER 408.4 |