Permit: T10CM00778

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T10CM00778

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2010 ELECTRIC - UFER Approved IVRS - Inspection :*
07/23/2010 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
1) FINISH ALL PREVIOUS ITEMS BEFORE RECALL
07/22/2010 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOND METAL RACEWAY FOR GEC 250.64 (?)
2) CLOSE UNUSED CONDUIT OPENING ABOVE PANEL
3) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS AND FILL UNUSED OPENINGS
4) BOND CONTACTOR ENCLOSURE
5) FINISH INSTA HOTS AND LIGHTING AT SHELVES
6) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
7) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM FLOOR BOXES
8) PLEASE VERIFY LISTING FOR LIGHT ASSEMBLIES
9) SUPPORT M/C UP OFF FLOOR AT CASH BOX
10) PANEL DIRECTORY PER 408.4