Permit: T10CM00766

Parcel: 138201120


Addresses:

7018 S LEARY DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/02/2010 FRAMING Approved IVRS - Inspection :*
06/29/2010 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTERIOR GFCI NOT O9N PLAN SHOULD BE 12-2 WIRING CIRCUIT 12
2) APPROVED PLAN SHOWS SUB PANEL NEW LOCATION. SHOWS ALL LIGHTS AND EXHAUST FAN ON #12 WIRING CIRCUIT 10 ?
3) ALL DUCT WORK IN UNCONDITIONED SPACE REQUIRES R-8 INSULATION
4) BATH GFCI OUTLET 12-2 WIRING
5) MISSING NAILER STUD BATHROOM SOUTH EAST CORNER
06/22/2010 FRAMING Not ready for Inspection IVRS - Inspection :*
1) WORK NOT COMPLETE ENOUGH TO INSPECT
06/14/2010 FRAMING Not ready for Inspection IVRS - Inspection :*