Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/20/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED SEALED JOINTS ON DUCTING-OK TO INSULATE |
|
| 05/18/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : 1. PROVIDE DUCT TAKE-OFFS PER DETAIL 5 AND DRAWINGS. 2. SUPPLY DUCT IN SOFFIT NOT PROPERLY INSULATED. 3. REMOVE ALL INSULATION AND SEAL ALL TRANSVERSE DUCT SEAMS, SEALER TO BE INSPECTED PRIOR TO INSULATING DUCT. 4. PROVIDE SADDLES ON FLEX SUPPORT PER DETAILS 5. PROVIDE HIGH EFFICIENCY TAPS ON FLEX TAKE OFFS 6. FLEX DUCT CONNECTIONS TO BE PER DETAIL |