Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/19/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK #4 STILL NEED APPROVED ROMEX CONNECTORS IN SUB-PANEL AT WALK IN ALSO PLUG HOLE AT BOTTOM |
|
| 09/24/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO COMPLIANCE #4 & 5 |
|
| 06/08/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT CONDUIT PER CODE 3' AND 10' 2) INSTALL DISCONNECTS FOR FAN COILS 3) ROUGH WIRING COVERED PRIOR TO INSPECTION AND REMOVE DRYWALL BY EACH DEVICE BOX TO VIEW WIRING METHOD 4) COLOR CODING OF FEEDER CONDUCTORS INCORRECT 5) ROMEX TO BE TERMINATED WITH APPROVED CONNECTORS 6) DISC. S.W. FOR COMPRESSOR NOT SECURELY SUPPORTED 7) ALL PENETRATIONS OR QUALIFIED ELECTRICIAN TO DO WORK |