Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2010 | ELECTRIC - ABOVE CEILING | Approved | ||
| 04/01/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/31/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FINISH ITEMS #1, 2, 5 & 6 |
|
| 03/30/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT VDV CABLING PER 725.3 + 24, 800.3 + 20 AND 300.11 2) SECURELY ATTACH RELOCATED FIXTURES TO GRID 410.16 3) BROKEN FIXTURE WHIP 4) FIXTURE WHIP NOT TO LAY ON GRID 5) PLANS DO NOT SHOW EMERGENCY EGRESS ILLUMINATION, NO LIGHTS WORK FOR THIS-EXIT LIGHTS NOT WITH BATTERY BACK UP 6) PANEL SCHEDULE NOT PER CIRCUITS |
|
| 03/29/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ACCESS TO ABOVE GRID FOR ABOVE CEILING INSPECTION 2) REVISE PLAN TO SHOW WOOD SOFFIT CAN LIGHTING |