Permit: T10CM00741

Parcel: 105110690

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T10CM00741

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2010 ELECTRIC - ABOVE CEILING Approved
04/01/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/31/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) FINISH ITEMS #1, 2, 5 & 6
03/30/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT VDV CABLING PER 725.3 + 24, 800.3 + 20 AND 300.11
2) SECURELY ATTACH RELOCATED FIXTURES TO GRID 410.16
3) BROKEN FIXTURE WHIP
4) FIXTURE WHIP NOT TO LAY ON GRID
5) PLANS DO NOT SHOW EMERGENCY EGRESS ILLUMINATION, NO LIGHTS WORK FOR THIS-EXIT LIGHTS NOT WITH BATTERY BACK UP
6) PANEL SCHEDULE NOT PER CIRCUITS
03/29/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ACCESS TO ABOVE GRID FOR ABOVE CEILING INSPECTION
2) REVISE PLAN TO SHOW WOOD SOFFIT CAN LIGHTING