Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM00717
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 04/21/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT USE WHITE WIRE TO POWER DISCONNECT 2) PROVIDE A NEUTRAL WHITE WIRE FOR SERVICE RECEPT 3) PLASTIC OVERFLOW SENSOR TO CLOSE TO VENT CONNECTOR, PROVIDE 6" CLEARANCE 4) FITTING ON VENT CONNECTOR UPSIDE DOWN |
|
| 03/30/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN 2) PROVIDE A SEDIMENT TRAP IN GAS LINE 3) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR 4) PROVIDE UV RATED STAT WIRE AT CONDENSOR 5) SUPPORT AND SECURE THE ELECTRIC DISCONNECT 6) DO NOT USE WHITE WIRE FOR POWER TO CONDENSOR 7) USE ONLY OUTDOOR FITTINGS TO CONNECT ELECTRIC CONDUIT TO DISCONNECT ON ROOF 8) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF |
|
| 03/26/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |