Inspection History: MECHANICAL - FINAL

Permit Number - T10CM00717

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
04/21/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DO NOT USE WHITE WIRE TO POWER DISCONNECT
2) PROVIDE A NEUTRAL WHITE WIRE FOR SERVICE RECEPT
3) PLASTIC OVERFLOW SENSOR TO CLOSE TO VENT CONNECTOR, PROVIDE 6" CLEARANCE
4) FITTING ON VENT CONNECTOR UPSIDE DOWN
03/30/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN
2) PROVIDE A SEDIMENT TRAP IN GAS LINE
3) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR
4) PROVIDE UV RATED STAT WIRE AT CONDENSOR
5) SUPPORT AND SECURE THE ELECTRIC DISCONNECT
6) DO NOT USE WHITE WIRE FOR POWER TO CONDENSOR
7) USE ONLY OUTDOOR FITTINGS TO CONNECT ELECTRIC CONDUIT TO DISCONNECT ON ROOF
8) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
03/26/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*