Permit: T10CM00713

Parcel: 13815014G


Addresses:

434 W LERDO RD 02


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM00713

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR TILES MECHANICAL ONLY
07/07/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SEAL ALL DUCT JOINTS
2) PROVIDE APPROVED DUCT HANGERS
3) FLEX DUCT NOT TO EXCEED 6' PER PLANS M0.1 MECH SPECS DUCT WORK 11
4) FLEX DUCT SUPPORT NOT TO EXCEED 3' ON CENTER PER DETAIL 3 M3.1
5) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX CONNECTIONS
06/23/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) BATHROOM HARD LIDS OK