Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR TILES MECHANICAL ONLY |
|
| 07/07/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SEAL ALL DUCT JOINTS 2) PROVIDE APPROVED DUCT HANGERS 3) FLEX DUCT NOT TO EXCEED 6' PER PLANS M0.1 MECH SPECS DUCT WORK 11 4) FLEX DUCT SUPPORT NOT TO EXCEED 3' ON CENTER PER DETAIL 3 M3.1 5) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX CONNECTIONS |
|
| 06/23/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BATHROOM HARD LIDS OK |