Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM00713
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 2) MAINTAIN WORKING SPACE AT WATER HEATER DISCONNECT 110.26 3) NEED BUSHING ON FEEDER CONDUIT 356.62 AND 300.4 4) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL 5) EM LIGHTING IN WORKING CLASSROOM #4 6) EXTERIOR EM LIGHTING NOT WORKING 7) RESTROOM INCORRECTLY LABELED TO CIRCUIT 8) BLDG DISCONNECT-ONLY ONE CONDUCTOR PER LUG 250.80 AND 250.12-CANNOT STACK LUGS AND DOOR IS NOT LOCKING CLOSED WITH LATCH ROOF: 1) TIGHTEN ALL FITTINGS 2) LABEL DISCONNECTS 3) PROTECT SEAL TIGHT GROM SHARP METAL EDGES 4) RECEPT COVERS TO BE PER 406.8 |