Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/01/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) LABELING IS NEEDED FOR 690.17 2) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 3) GROUNDING ELECTRODE CONDUCTOR CANNOT BE PARALLEL AT TAPED WITH #6'S 4) SERVICE GUTTER TO BE REFLECTIVE OF CORRECT NUMBER OF DISCONNECTS 230.71(A) 5) OK ROOF |