Permit: T10CM00709

Parcel: 12901035L


Addresses:

140 S TUCSON BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM00709

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/23/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/30/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS CALL FOR NEW PANEL 'S' NOT INSTALLED
2) SEPERATE BLDG SHOULD HAVE GROUNDING ELECTRODE SYSTEM PER 250.32 NEC
11/23/2011 ELECTRIC - FINAL Denied PLEASE HAVE ELECTRICAL CONTRACTOR ON SITE FOR INSPECTION
NO MESSAGE