Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2010 | MECHANICAL - INTERMEDIATE | Approved | ||
| 04/09/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NO MECHANICAL IN UNIT 1321 2) EXHAUST IN UNITS 1317, 1318 OK TO COVER |
|
| 04/08/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT #1317: 1) PROVIDE DUCTING FOR BATHROOM EXHAUST 2) COMBUSTIBLE MATERIAL NOT ALLOWED IN THE RETURN PLENIUM 3) REMOVE OR COVER ALL WOOD 4) USE CPVC OR COPPER IN PLENIUM FOR CONDENSATE PIPING 5) LEAVE OUT SHEETROCK IN RESTROOM TO CHECK EXHAUST DUCT. ALSO LEAVE OUT OF SOFFIT UNIT #1318: 1) PROVIDE EXHAUST DUCT |
|
| 04/07/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH ALL DUCTING & VENTING CONDENSATE PIPING UNITS 1318 & 1321 ARE LOCKED. |