Permit: T10CM00708

Parcel: 11202004C

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM00708

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2010 MECHANICAL - INTERMEDIATE Approved
04/09/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NO MECHANICAL IN UNIT 1321
2) EXHAUST IN UNITS 1317, 1318 OK TO COVER
04/08/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNIT #1317:
1) PROVIDE DUCTING FOR BATHROOM EXHAUST
2) COMBUSTIBLE MATERIAL NOT ALLOWED IN THE RETURN PLENIUM
3) REMOVE OR COVER ALL WOOD
4) USE CPVC OR COPPER IN PLENIUM FOR CONDENSATE PIPING
5) LEAVE OUT SHEETROCK IN RESTROOM TO CHECK EXHAUST DUCT. ALSO LEAVE OUT OF SOFFIT
UNIT #1318:
1) PROVIDE EXHAUST DUCT
04/07/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FINISH ALL DUCTING & VENTING CONDENSATE PIPING
UNITS 1318 & 1321 ARE LOCKED.