Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2010 | ELECTRIC - UNDERGROUND | Approved | ||
| 06/07/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUITS-SERVICE AND UNDERSLAB 2) REDUCING WASHERS IMPROPERLY INSTALLED 3) MAIN BONDING JUMPER AND GEC TO BE SAME LUG 4) CANNOT MODIFY LUGS 5) NEED REJECTION PINS |
|
| 06/01/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* |