Inspection History: ELECTRIC - FINAL
Permit Number - T10CM00692
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EM LIGHTING TO BE CONNECTED TO LIGHTING CIRCUIT FEEDING AREA SEE NOT #8 2) BATHROOM RECEPT TO BE GFI PROTECTED 3) BONDING JUMPER TO DISCONNECT ENCLOSURE FOR WATER HEATER TO BE #10 FOR 30 AMP CIRCUIT |