Permit: T10CM00692

Parcel: 128100810

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM00692

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/06/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EM LIGHTING TO BE CONNECTED TO LIGHTING CIRCUIT FEEDING AREA SEE NOT #8
2) BATHROOM RECEPT TO BE GFI PROTECTED
3) BONDING JUMPER TO DISCONNECT ENCLOSURE FOR WATER HEATER TO BE #10 FOR 30 AMP CIRCUIT