Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE SERVICE RECEPT WITHIN 25' OF RTU, PROVIDE WITH GFI AND BUBBLE COVER 2) DO NOT RUN LINE VOLTAGE HOT LEGS WITH WHITE WIRE 3) PROVIDE 3/4" PVC CONDENSATE, TERMINATE WITHIN 6" OF GRADE, COAT TO PROTECT FROM SUN LIGHT |