Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/31/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLAN CALLS FOR FUSED A/C DISCONNECT AT INVERTER 2) PLANS DO NOT SHOW PV DATA MONITORING UNIT AND THE 2 RECEPTS IN UNIT-HOW ARE THESE POWERED AND WHAT CIRCULATING 3) LABELING NEEDED FOR SHOCK HAZARD AS NOTE #3 ON PLANS AND ARTICLE 690.17 4) MAINTAIN WORKING CLEARANCES AT A/C DISCONNECT AT INVERTER AND AT SERVICE 110.26 5) OK ROOF |